Product Enquiry
From initial contact through installation, service, maintenance to disposal, KUP provides its customers with an unrivalled single source for complete power protection.
Ideal for: mid-size server rooms, networks, telecommunications systems, and life safety applications
Standalone three-phase UPS system available in seven power ratings from 10 to 50kVA and in different cabinet sizes enabling you to choose a compact system with the ideal internal battery capacity for your critical load. A true online, double conversion, VFI (voltage frequency independent) UPS system that offers exceptional reliability and unprecedented power availability for mid-size server rooms, networks, telecommunication systems and industrial processes.
Compact UPS power supply system with intelligent battery management, 95.5% efficiency and a low carbon footprint. Delivers excellent value for money without compromising on performance.
Redundant critical circuits (RCC) duplicate the critical components and circuitry within the KOHLER PW 5000/TP to maximise productivity and minimise downtime.
Innovative transformerless design and Energy Saving Inverter Switching (ESIS) technology ensures high efficiency to reduce the total cost of ownership. Temperature controlled battery chargers extend lifetime performance to reduce running costs.
Compact design maximises floor space with a footprint of 0.4m2 at 50 kVA. A power density of up to 100kW/m2 saves space for other IT equipment.
Available in three cabinet sizes, the 3 phase uninterrupted power supply offers flexible capacity for critical loads. The 10 to 25kVA units are available in two cabinet sizes and the 30 – 50 kVA units are housed in a larger cabinet to accommodate different configurations of internal batteries.
Additional battery cabinets that match perfectly with the UPS for scaling autonomy time.
Designed with state-of-the-art energy efficiency of up to 95.5%, the KOHLER PW 5000/TP helps to reduce carbon footprint and running costs.
To request more details about the KOHLER PW 5000/TP make an enquiry using the form below or call us on +353 (0)1 4606859.
Actual kVA | 10-50kVA |
---|---|
Type | Three-Phase |
Standalone / Modular | Standalone |
Max. power per frame with N+1 redundancy | Up to 20kVA N+1 |
Parallelable up to | 20 units (1MVA) |
Rated output voltage range | 380/220; 400/230; 415/240V Three-Phase |
Working mode | Online double conversion |
Power density per m2 | Up to 112kWm2 / 125kVA/m2 |
Battery compartment | Included in UPS cabinet |
Maintenance bypass | Standard |
Network/web interface | Option |
Volt free contacts | Standard |
Input current distortion THDi @100% load | < 3% |
Scalable (N+1) | Yes (horizontal) |
Hot-swappable modules | No |
From initial contact through installation, service, maintenance to disposal, KUP provides its customers with an unrivalled single source for complete power protection.
Whether considering design concepts for a new facility or how to tackle an upgrade, our trusted experts are on hand to help you find an efficient, resilient system and service package that works for you.
Or why not give us a call on +353 (0)1 4606859 and chat directly to a member of our team.